How the Dehumidifier Sizing Calculator works

Last updated:

Last data update: 2026-08-24.

Data

Sizing grid (pints/day under the 2019 DOE rating, by floor area × dampness) reproduced from an AHAM DH-1-2022-style chart via a third-party source, cross-checked against ENERGY STAR's published bands (moderately damp < 2,000 sq ft: 20–30; very damp: 25–40; wet: 30–50). Three of the four dampness descriptions are ENERGY STAR's (moderately damp, very damp, wet); "slightly damp" follows the AHAM chart.

area  slightly  moderately  very  wet
500     10        14         18    26
1000    14        20         26    36
1500    18        26         34    46
2000    22        30         42    52
2500    26        34         46    56

Formula

Bilinear interpolation on area between grid rows; below 500 sq ft the 500 row is scaled by area/500 with a floor of 10; above 2,500 sq ft, +4 pints per additional 500 sq ft (cap 70) with a two-unit suggestion. Retail mapping: ≤ 22 → 20/22 pint; ≤ 35 → 30/35; otherwise 50; pump suggested for basements/pump drain.

2019 rating change

DOE Appendix X1 (65 °F / 60 % RH) replaced Appendix X (80 °F / 60 % RH) for compliance from June 13, 2019 (background in 88 FR 48035). ENERGY STAR's conversion table: 30→20, 40→25, 50→30, 55→30–35, 60→35, 70→40–45, 90→55 (portable units).

Change log

  • 2026-08-24 — first release.

Cite this page

GridComfort, "Dehumidifier Sizing Calculator — methodology," https://gridcomfort.com/tools/dehumidifier-sizing-calculator/methodology/, data updated 2026-08-24.