Rheem Furnace Codes by Series

RheemRheem gas furnaces covered by thirteen Rheem installation manuals: (-)801T, (-)801S/P, (-)92T, (-)95T, (-)96T, (-)802V, (-)96V, (-)97V, (-)98V and the older RGRM/RGTM, RGPR/RGLR, RGRK/RGRL/RGTK and RGRA-family furnacesLast updated:

A Rheem furnace shows a fault as a two-digit number on its display or, on older RGRM, RGPR, RGRK and RGRA-family furnaces, as blinks of a green status LED. The same number can mean different things between series, so find your series first. Every meaning below is copied from Rheem's own installation manual, with document number and page.

Key facts

FactDetail
Series covered13 Rheem manuals: (-)801T, (-)801S/P, (-)92T, (-)95T, (-)96T, (-)802V, (-)96V, (-)97V, (-)98V, RGRM/RGTM, RGPR/RGLR, RGRK/RGRL/RGTK, RGRA/RGRB/RGTA/RGRS/RGTS/RGRT
Where the meanings come fromRheem installation instructions 92-24161-144-09, -142-15, -154-03, -120-16, -157-04, -148-07, -124-12, -126-04, -159-03, -84-11, -49-10, -36-26 and -16-20, all on Rheem's own document server
Display series(-)801T and (-)801S/P (one seven-segment digit); (-)92T, (-)95T, (-)96T (seven-segment display); (-)802V, (-)96V, (-)97V, (-)98V (dual seven-segment display)
LED seriesRGRM/RGTM (FLAME, STATUS, POWER and CFM LEDs); RGPR/RGLR, RGRK/RGRL/RGTK and the RGRA family (green STATUS LED, amber FLAME LED)
Readings that are not faults0 (standby), C, F, H and h, plus HP, dF and Cd on the communicating series
What the manuals leave to an ownerKeeping the air filters clean and the area around the furnace clear; flame sensor cleaning and the annual inspection go to a qualified installer, service agency or the gas supplier
Last checkedOctober 20, 2026

How to find your series

The model number is on the furnace's rating plate. Rheem's manuals say so in one line: "See name/rating plate and clearance label for specific model number and clearance information." (92-24161-144-09, p. 8). They do not explain how to decode the model letters, so this page does not either. The current manuals print the brand letter as a placeholder, "(-)96V SERIES & (-)(-)96MDV SERIES", so match the letters and digits that follow it.

Series as Rheem prints itManual (revision used here)How it shows a faultSection
(-)801T / (-)(-)80MSX92-24161-144-09One seven-segment digitjump
(-)801S / (-)801P / (-)(-)80MSS / (-)(-)80MSP92-24161-142-15One seven-segment digitjump
(-)92T / (-)(-)92MSX92-24161-154-03Seven-segment displayjump
(-)95T / (-)(-)95MSX92-24161-120-16Seven-segment displayjump
(-)96T / (-)(-)96MDT92-24161-157-04Seven-segment displayjump
(-)802V / (-)(-)80MDV92-24161-148-07Dual seven-segment displayjump
(-)96V / (-)(-)96MDV92-24161-124-12Dual seven-segment displayjump
(-)97V and (-)98V92-24161-126-04, 92-24161-159-03Dual seven-segment displayjump
RGRM / RGTM92-24161-84-11FLAME, STATUS, POWER and CFM LEDsjump
RGPR / RGLR, RGRK-12ERAJS / RGRL / RGTK92-24161-49-10, 92-24161-36-26Green STATUS LED, amber FLAME LEDjump
RGRA / RGRB / RGTA / RGRS / RGTS / RGRT92-24161-16-20Green LED, amber FLAME LEDjump

Ruud furnaces are made by the same company, but Rheem's documents don't list which Ruud models use these tables, so check your own furnace's installation manual.

How to read a Rheem code

On the display series a number is the code, and on the single-digit (-)801T and (-)801S/P display it arrives one digit at a time. Rheem's wording (92-24161-144-09, p. 39): "The method for displaying a two-digit fault is to display the first (most significant) digit for one second immediately followed by the second digit – which is also displayed for a duration of one second. A ½ second pause is then displayed. Cycle repeats until the fault is cleared. Each fault is flashed (displayed) a minimum of two times even if the fault condition has cleared before the fault can be displayed twice."

The same page explains the standby and mode letters: "During standby mode with no fault codes present, the display will read "0" (zero). During normal thermostat heating, cooling or continuous fan operation, a letter will be displayed to describe the mode of operation as follows: C = Cooling or Heat-Pump Heat Operation F = Continuous Fan Operation H = Gas Heating Operation". When two faults are present, the display alternates them with the top segment lit for ½ second between.

The communicating manuals add a warning worth reading before anything else (92-24161-124-12, p. 111): "NOTE: Verify display orientation is correct before interpreting fault codes. Otherwise, the fault codes may be upside-down. If a fault code or operating code is not on these lists, the display may be upside-down."

Lockouts and how they clear

Several codes are lockouts rather than faults in themselves: 10 on the display series, one blink on the LED series. Rheem's single-stage manual (92-24161-144-09, p. 40) says: "All lockout conditions can be cleared immediately provided that the original fault causing the lockout is cleared and power to the unit is cycled off and then back on again or (soft lockout only) if a heat call is cycled off for greater than 2 seconds but less than 20 seconds."

A one-hour lockout starts when "Flame has not been detected after four ignition trials", "Flame has been lost for five times in one heat call", "Undesired flame has been detected", "Dead Blower has been detected (main limit circuit open for more than 150 seconds)" or "When voltage has unexpectedly been detected on the gas valve circuit and voltage goes away when inducer is shut off." It "will automatically be reset after one hour". A hard lockout with code 93 "cannot be reset by cycling the heat call."

The older LED flowcharts give a power reset in a note (92-24161-49-10, p. 41): "NOTE: If IFC goes into lockout ("STATUS" LED will flash code "1"), shut off main power to unit, wait 30 seconds and then reset power." Clearing a lockout does not fix what caused it. A code that comes back is a call for a qualified servicer.

801T and 801S/P codes (80% single stage)

These 80% single-stage furnaces have one seven-segment digit and the shortest code list. The (-)801T manual 92-24161-144-09 and the (-)801S / (-)801P manual 92-24161-142-15 print the same table on p. 39, word for word, including the spelling "CONTINUOS".

Rheem (-)801T and (-)801S/P display codes, 92-24161-144-09 and 92-24161-142-15, p. 39
CodeRheem's description (verbatim)Page
0STANDBY39
101 HOUR LOCKOUT39
11FAILED IGNITION39
12LOW FLAME SENSE39
13FLAME LOST39
14UNEXPECTED FLAME39
20TWINNING FAULT39
22MAIN LIMIT OR HALC OPEN39
26LINE AND NEUTRAL REVERSED39
33MRLC (MANUAL RESET LIMIT CONTROL) (AKA ROLL-OUT) OPEN39
55PRESSURE SWITCH STUCK CLOSED WHEN SHOULD BE OPEN39
57PRESS SWITCH STUCK OPEN WHEN SHOULD BE CLOSED39
61BLOWER FAULT – BLOWER UNABLE TO RUN39
93INTERNAL CONTROL FAULT39
CCOMPRESSOR ON (COOLING OR HEAT-PUMP HEAT)39
HGAS HEAT ON39
FCONTINUOS FAN ON39

Page 39 also sets out which pairs appear together: four failed ignitions show 10 and 11, five flame losses show 10 and 13, unexpected flame shows 14 and 10, and a dead blower shows 61 and 10, or 61 and 22 while the main limit stays open.

92T and 95T codes (90%+ single stage)

The condensing single-stage furnaces use the same list plus two water-sensing codes, 58 and 59, and print 22 as "MAIN LIMIT OPEN". Manuals 92-24161-154-03 ((-)92T) and 92-24161-120-16 ((-)95T) carry the identical Table 17, "90P 1 STAGE FAULT CODE LIST", on p. 87.

Rheem (-)92T and (-)95T display codes, Table 17, 92-24161-154-03 and 92-24161-120-16, p. 87
CodeRheem's description (verbatim)Page
0STANDBY87
101 HOUR LOCKOUT87
11FAILED IGNITION87
12LOW FLAME SENSE87
13FLAME LOST87
14UNEXPECTED FLAME87
20TWINNING FAULT87
22MAIN LIMIT OPEN87
26LINE AND NEUTRAL REVERSED87
33MRLC (MANUAL RESET LIMIT CONTROL) (AKA ROLL-OUT) OPEN87
55PRESSURE SWITCH STUCK CLOSED WHEN SHOULD BE OPEN87
57PRESS SWITCH STUCK OPEN WHEN SHOULD BE CLOSED87
58WATER SENSE CIRCUIT OPEN87
59WATER SENSED87
61BLOWER FAULT – BLOWER UNABLE TO RUN87
93INTERNAL CONTROL FAULT87
CCOMPRESSOR ON (COOLING OR HEAT-PUMP HEAT)87
HGAS HEAT ON87
FCONTINUOUS FAN ON87

Table 20 of each manual (pp. 88–94) gives every fault a description, cause and solution written for the installer; it is not reproduced here.

96T codes (two stage)

The two-stage (-)96T adds a lower-case h for low-stage heat and splits the pressure-switch faults into low and high switches (44 to 57). It is also the only table here with a fault priority column; the manual's text says that when two or more codes are present at the same time, priority decides how they are displayed (p. 88). This is Table 17, "90P 2 STAGE FAULT CODE LIST", of 92-24161-157-04, p. 88, including its spelling "INIDUCER".

Rheem (-)96T display codes with fault priority, Table 17, 92-24161-157-04, p. 88
CodeRheem's description (verbatim)Fault Priority
0STANDBY24
101 HOUR LOCKOUT13
11FAILED IGNITION15
12LOW FLAME SENSE14
13FLAME LOST16
14UNEXPECTED FLAME2
20TWINNING FAULT20
22MAIN LIMIT OPEN4
26LINE AND NEUTRAL REVERSED17
33MRLC (MANUAL RESET LIMIT CONTROL) (AKA ROLL-OUT) OPEN3
44LOW PRESSURE SWITCH CLOSED6
45LOW PRESSURE SWITCH OPEN, INDUCER ON HIGH SPEED8
46LOW PRESSURE SWITCH OPEN, INIDUCER ON LOW SPEED9
55HIGH PRESSURE SWITCH CLOSED7
57HIGH PRESSURE SWITCH OPEN11
58DRAIN CIRCUIT OPEN10
59BLOCKED DRAIN12
61BLOWER FAULT – BLOWER UNABLE TO RUN18
93INTERNAL FAULT1
CCOMPRESSOR ON (COOLING OR HEAT-PUMP HEAT)22
HHIGH GAS HEAT ON21
hLOW GAS HEAT ON19
FCONTINUOUS FAN ON23

802V, 96V, 97V and 98V codes (communicating)

The communicating furnaces share one longer list, with memory-card codes (d1, d4, d6), separate main limit and HALC codes (22, 23), an open fuse (30) and blower codes (60, 66, 68). Their tables name each code and give a status line saying whether the furnace keeps running. The modulating (-)97V and (-)98V add four codes: 65, 67, 71 and 77.

The table gives each code's displayed text and the first sentence or two of its STATUS line, verbatim, from the (-)96V manual 92-24161-124-12, Table 20, pp. 112–120. The full DESCRIPTION, EXPECTED OPERATION, CAUSE and SOLUTION columns are written for service personnel and are not reproduced. The last column shows where each code appears in the other three manuals.

Rheem communicating furnace fault codes: displayed text and status, verbatim, 92-24161-124-12 Table 20 with the (-)802V, (-)97V and (-)98V tables
CodeDisplayed text (verbatim)Status (verbatim)Page in 96V / 802V / 97V / 98V
d1NO MODEL DATAThis is a critical fault. The furnace will not operate in any mode.112 / 65 / 95 / 92
d4NO VALID MODEL DATA ON MEMORY CARD (97V, 98V: ON MODEL DATA CARD)This is a non-critical fault. The furnace should operate in any mode.112 / 65 / 95 / 92
d6HORSEPOWER CONFLICT ON MEMORY CARD (97V, 98V: ON MODEL DATA CARD)This is a non-critical fault. The furnace should operate in any mode.112 / 65 / 95 / 92
10ONE-HOUR LOCKOUTThis is a critical fault. The furnace will not operate in gas heat modes but all other modes (e.g. cooling) should function.113 / 66 / 96 / 93
11FAILED IGNITIONUp to three failed ignitions will not constitute a critical condition.113 / 66 / 96 / 93
12LOW FLAME SENSEThe status of this fault is non-critical and furnace operation will continue as normal in heating (and all other) mode(s).114 / 67 / 97 / 94
13FLAME LOST AFTER ESTABLISHEDFlame loss is not a critical fault. Subsequent ignition attempts will follow and normal operation should resume.114 / 67 / 97 / 94
14FLAME PRESENT WITH GAS VALVE OFFThis is an extremely critical fault and should rarely (if ever) be seen in the field.114 / 67 / 97 / 94
22MAIN LIMIT OPENThis is a critical fault. The furnace will not operate in gas heat modes but all other modes (e.g. cooling) should function.115 / 68 / 98 / 95
23HALC OPENThis is a critical fault. The furnace will not operate in gas heat modes but all other modes (e.g. cooling) should function.115 / 68 / 98 / 95
26LINE AND NEUTRAL REVERSED OR POOR GROUNDThis is a critical fault. The furnace will not operate in gas heat or any other modes.115 / 68 / 98 / 95
30OPEN FUSEThis is a critical fault. The furnace will not operate in any mode.116 / 69 / 99 / 96
33OVER-TEMPERATURE SWITCH (ROLL-OUT) OPEN (802V adds "(AKA MRLC)")This is a critical fault. The furnace will not operate in gas heat modes but all other modes (e.g. cooling) should function.116 / 69 / 99 / 96
44LOW PRESSURE SWITCH CLOSED, INDUCER OFFThis is a critical fault. The furnace will not operate in gas heat modes but all other modes (e.g. cooling) should function if present simultaneously with a heating call (e.g. defrost call in dual-fuel mode).116 / 69 / 99 / 96
45LOW PRESSURE SWITCH OPEN, INDUCER ON HIGH SPEEDSame status as 44117 / 70 / 100 / 97
46LOW PRESSURE SWITCH OPEN, INDUCER ON LOW SPEEDSame status as 44117 / 70 / 100 / 97
55HIGH PRESSURE SWITCH CLOSED, INDUCER OFFSame status as 44118 / 71 / 101 / 98
57HIGH PRESSURE SWITCH OPEN, INDUCER ON HIGH SPEEDSame status as 44118 / 71 / 101 / 98
58WATER CIRCUIT OPENThis is a critical fault experienced by the furnace. The furnace will not operate in gas heat modes but all other modes (e.g. cooling) should function if a call is present.118 / 71 / 101 / 98
59WATER SENSEDSame status as 58119 / not listed / 102 / 99
60BLOWER FAULT - BLOWER CAN STILL RUNThis is a non-critical fault experienced by the furnace.119 / 72 / 102 / 99
61BLOWER FAULT - MOTOR CANNOT RUNThis is a critical fault. The furnace will not operate in any mode.119 / 72 / 102 / 99
65MID PRESSURE SWITCH CLOSED, SHOULD BE OPENThis is a non-critical fault. The furnace will operate in gas heat modes but gas heat firing rate demands from the thermostat between 50% and 65% will operate at 70% instead.97V p. 103 / 98V p. 100 only
66BLOWER CUTBACKThis is a non-critical fault experienced by the furnace.120 / 73 / 103 / 100
67MID PRESSURE SWITCH OPEN, SHOULD BE CLOSEDSame status as 6597V p. 103 / 98V p. 100 only
68NO BLOWER COMMUNICATIONSThis is a critical fault. The furnace will not operate in any mode.120 / 73 / 104 / 101
71INDUCER FAULTSame status as 4497V p. 104 / 98V p. 101 only
77NO GAS VALVE FEEDBACK SIGNALSame status as 4497V p. 104 / 98V p. 101 only
93INTERNAL CONTROL FAULT DETECTEDThis is a critical fault. The furnace will not operate in any mode of operation.120 / 73 / 104 / 101
99REMOTE FAULTS RESET PERFORMEDThis is a notification that fault codes in the fault buffer have been reset.120 / 73 / 104 / 101

Codes 65 and 67 on the modulating furnaces are non-critical, and gas heat carries on; in Rheem's words for both, "Gas heating will proceed as normal except firing rates between 50% and 65% will be fixed to 70% by the furnace control." (92-24161-126-04, p. 103.)

Each of these manuals also has a normal operation table (802V Table 12 p. 64; 96V Table 19 p. 111; 97V Table 18 p. 94; 98V Table 18 p. 91). None of these readings is a fault:

Rheem communicating furnace normal operation codes, verbatim names, 92-24161-124-12 Table 19, p. 111
CodeName (verbatim)Rheem's description, first sentence (verbatim)
0STANDBY MODEThis code is displayed anytime there is no fault present and no thermostat call present.
H or hGAS HEAT MODEThis code is displayed anytime there is a call for gas heat.
C or cCOOLING MODEThis code is displayed anytime there is a call for cooling.
HP or hPHEAT-PUMP HEATING MODEThis code is displayed anytime there is a call for heat-pump heat.
FCONTINUOUS FAN MODEThis code is displayed anytime there is a call for continuous fan from the thermostat.
dFDEFROST MODEThis code indicates that the heat-pump is in defrost mode (dual-fuel systems only) and furnace is operating for defrost operation which is fixed at low-stage gas heating operation.
Cd or cdCOOLING IN DE-HUMIDIFICATION MODEThis code indicates that there is a both cooling and de-humidification demand present at the same time.

On these furnaces the lower-case letter is the low stage; for gas heat Rheem says "The lower-case "h" is displayed when the thermostat is requesting low gas heat and the upper-case "H" is displayed when the thermostat is requesting high-stage gas heat."

RGRM and RGTM LED codes

These two-stage condensing furnaces have four LEDs, labelled flame, status, power and CFM, and the manual explains each in a short legend. "There are four diagnostic LED's on the furnace control. These are labeled flame, status, power and CFM." (92-24161-84-11, p. 55). The legend below is p. 56.

Rheem RGRM / RGTM LED codes, 92-24161-84-11, p. 56
LED and signalRheem's description (verbatim)Page
FLAME LED: OFFNo flame is detected.56
FLAME LED: Rapid BlinkUnexpected Flame56
FLAME LED: Slow BlinkMarginal Flame Sense56
FLAME LED: Steady ONNormal Flame Detected56
STATUS LED: Steady ONNormal Fault detected.56
STATUS LED: 1 BlinkIgnition failure – 1 HR lockout56
STATUS LED: 2 BlinksPressure switch stuck open – switch will not close when inducer is on.56
STATUS LED: 3 BlinksLimit switch open – main limit or roll-out control.56
STATUS LED: 4 BlinksPressure switch stuck closed. Switch will not open.56
STATUS LED: 5 BlinksNot applicable.56
STATUS LED: 6 BlinksLine and Neutral reversed.56
POWER LED: OFFNo power (24VAC) to control board.56
POWER LED: ONControl is powered.56
CFM LEDOne Blink represents 100 CFM of target airflow. A half blink represents approx. 50 CFM.56

The manual adds that the CFM LED "is intended to be for reference only." "Normal Fault detected." is how the manual prints the steady status light.

These two-stage furnaces print their blink codes in a box on the troubleshooting flowchart, and the two manuals print the same box word for word: 92-24161-49-10 (RGPR / RGLR) Figure 33 on p. 41, and 92-24161-36-26 (RGRK-12ERAJS / RGRL / RGTK) Figure 53 on p. 60. The "Go to point" references are to letters on that flowchart, which is written for a trained service technician.

Rheem RGPR / RGLR and RGRK / RGRL / RGTK blink codes, 92-24161-49-10 p. 41 and 92-24161-36-26 p. 60
LED and signalRheem's description (verbatim)Pages
STATUS (Green) LED: 1 BlinkSoft lockout Reset System power and start over from beginning41 / 60
STATUS (Green) LED: 2 BlinksPS Circuit open Go to point "F"41 / 60
STATUS (Green) LED: 3 BlinksLimit circuit open Go to point "D"41 / 60
STATUS (Green) LED: 4 BlinksPS Circuit closed. Go to point "G"41 / 60
STATUS (Green) LED: 5 BlinksTwin Fault. Go to point "H"41 / 60
STATUS (Green) LED: 6 Blinks"Line" & "Neutral" Reversed or IFC not properly grounded.41 / 60
FLAME (Amber) LED: No BlinkNo Flame41 / 60
FLAME (Amber) LED: Slow BlinkMarginal Flame Sensed41 / 60
FLAME (Amber) LED: Rapid BlinkUnexpected Flame Sensed41 / 60
FLAME (Amber) LED: Steady OnGood Flame Present41 / 60

The RGRA, RGRB, RGTA, RGRS, RGTS and RGRT furnaces share one manual, 92-24161-16-20, whose Figure 54 on p. 56 is titled for "MODELS W/INTEGRATED FURNACE CONTROL (IFC) UT Electronic Controls 1012-925 (115 VAC IGNITER)". Its list stops at five blinks and marks the twinning code optional.

Rheem RGRA family blink codes, Figure 54, 92-24161-16-20, p. 56
LED and signalRheem's description (verbatim)Page
BLINK CODES (GREEN LED): 1 BlinkSoft lockout Reset System power and start over from beginning56
BLINK CODES (GREEN LED): 2 BlinksPS Circuit open go to point "F."56
BLINK CODES (GREEN LED): 3 BlinksLimit circuit open go to point "D."56
BLINK CODES (GREEN LED): 4 BlinksPS Circuit closed Go to point "G."56
BLINK CODES (GREEN LED): 5 BlinksTwin Fault (Optional) *Go to point "H."56
FLAME (AMBER) LED: OFFNo Flame Present56
FLAME (AMBER) LED: RAPID BLINKUnexpected Flame56
FLAME (AMBER) LED: SLOW BLINKMarginal Flame Sense56
FLAME (AMBER) LED: STEADY ONNormal Flame Sense56

The same figure carries the lockout note: "NOTE: If IFC goes into lockout ("STATUS LED will blink code "1"), shut off main power to unit, wait 30 seconds and then reset power."

Same code, different meaning

These are the places where Rheem's own documents give one code or blink count different wording or a different meaning. Read your own series' table, not the nearest number.

CodeWhere it means one thingWhere it means another
22(-)801T, (-)801S/P (p. 39): "MAIN LIMIT OR HALC OPEN"(-)92T, (-)95T, (-)96T: "MAIN LIMIT OPEN"; communicating series split it into 22 "MAIN LIMIT OPEN" and 23 "HALC OPEN"
55Single-stage series: "PRESSURE SWITCH STUCK CLOSED WHEN SHOULD BE OPEN"(-)96T: "HIGH PRESSURE SWITCH CLOSED"; communicating: "HIGH PRESSURE SWITCH CLOSED, INDUCER OFF"
57Single-stage series: "PRESS SWITCH STUCK OPEN WHEN SHOULD BE CLOSED"(-)96T: "HIGH PRESSURE SWITCH OPEN"; communicating: "HIGH PRESSURE SWITCH OPEN, INDUCER ON HIGH SPEED"
58 / 59(-)92T, (-)95T: "WATER SENSE CIRCUIT OPEN" / "WATER SENSED"(-)96T: "DRAIN CIRCUIT OPEN" / "BLOCKED DRAIN"; (-)802V lists 58 "WATER CIRCUIT OPEN" and no 59
61Display series without a communicating blower: "BLOWER FAULT – BLOWER UNABLE TO RUN"Communicating: "BLOWER FAULT - MOTOR CANNOT RUN", with 60 "BLOWER FAULT - BLOWER CAN STILL RUN" as a separate, non-critical code
93(-)801T, (-)801S/P, (-)92T, (-)95T: "INTERNAL CONTROL FAULT"(-)96T: "INTERNAL FAULT"; communicating: "INTERNAL CONTROL FAULT DETECTED"
1 blinkRGRM / RGTM: "Ignition failure – 1 HR lockout"RGPR, RGRK and RGRA families: "Soft lockout Reset System power and start over from beginning"
2 / 4 blinksRGRM / RGTM: "Pressure switch stuck open…" / "Pressure switch stuck closed…"Other LED families: "PS Circuit open" / "PS Circuit closed"
5 blinksRGRM / RGTM: "Not applicable."RGPR and RGRK families: "Twin Fault."; RGRA family: "Twin Fault (Optional)"
6 blinksRGRM / RGTM: "Line and Neutral reversed."RGPR and RGRK families: "“Line” & “Neutral” Reversed or IFC not properly grounded."; RGRA family: no six-blink code

What an owner can do, and what Rheem leaves to a servicer

Rheem's manuals are written for installers, and the maintenance chapter opens by saying so: "THESE INSTRUCTIONS ARE INTENDED AS AN AID TO QUALIFIED SERVICE PERSONNEL FOR PROPER INSTALLATION, ADJUSTMENT AND OPERATION OF THIS UNIT." What they ask the installer to tell the homeowner is short:

TaskRheem's wording (verbatim)Who
Filters"Keep the air filters clean. The heating system will operate better, more efficiently and more economically." ("Advise the customer", 92-24161-144-09 p. 49)Owner
Never without filters"DO NOT OPERATE THE SYSTEM FOR EXTENDED PERIODS WITHOUT FILTERS." (92-24161-144-09 p. 48)Owner
Where the filter is"Have your qualified installer, service agency or the gas supplier instruct you on how to access your filters for regular maintenance." (92-24161-84-11 p. 55)Installer shows the owner
Clear space"THE HOMEOWNER SHOULD BE CAUTIONED THAT THE FURNACE AREA MUST NOT BE USED AS A BROOM CLOSET OR FOR ANY OTHER STORAGE PURPOSES." (92-24161-144-09 p. 9)Owner
Flame sensor"It is recommended that at the beginning of the heating season, the flame sensor be cleaned with fine steel wool or Scotch Bright Pad by a qualified installer, service agency or the gas supplier." (92-24161-144-09 p. 49)Qualified installer, service agency or gas supplier
Burner flames"…a visual inspection be made of the main burner flames for the desired flame appearance by a qualified installer, service agency or the gas supplier." (92-24161-144-09 p. 49)Qualified installer, service agency or gas supplier
Annual inspection"…it is recommended that a qualified installer, service agency, or the gas supplier annually inspect the flue passageways, the vent system and the main burners for continued safe operation." (92-24161-144-09 p. 49)Qualified installer, service agency or gas supplier
Motor lubrication"IMPORTANT: DO NOT attempt to lubricate the bearings on the blower motor or the induced draft blower motor." (92-24161-144-09 p. 48)Nobody
Parts"Homeowners please visit www.rheem.com for product information." (92-24161-144-09 p. 49)Owner

Unlike Goodman's manuals, Rheem's do not leave the burner-flame check to the owner: it is assigned to a qualified installer, service agency or the gas supplier. Everything a fault code's solution column describes, from pressure switches to flame sensors, is servicer work.

Rheem's gas and carbon monoxide wording

Every manual cited here prints the gas-smell instruction on its cover (p. 1), and the covers of the (-)801T, (-)801S/P, (-)92T, (-)95T, (-)96T, (-)802V, (-)96V and (-)98V manuals add a carbon monoxide warning box. The furnace pages on this site carry the general guidance above; this is Rheem's own wording.

Rheem's wording (verbatim)Source
"WHAT TO DO IF YOU SMELL GAS • Do not try to light any appliance. • Do not touch any electrical switch; do not use any phone in your building. • Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's instructions. • If you cannot reach your gas supplier, call the fire department. • Do not return to your home until authorized by the gas supplier or fire department."92-24161-124-12, p. 1 (the same instruction is on the cover of all thirteen manuals)
"DO NOT RELY ON SMELL ALONE TO DETECT LEAKS. DUE TO VARIOUS FACTORS, YOU MAY NOT BE ABLE TO SMELL FUEL GASES."92-24161-124-12, p. 1
"U.L. and/or C.S.A. recognized fuel gas and CO (carbon monoxide) detectors are recommended in all applications, and their installation should be in accordance with the manufacturer's recommendations and/or local laws, rules, regulations, or customs."92-24161-124-12, p. 1 (92-24161-84-11 p. 1 reads "U.L. recognized fuel gas and CO (carbon monoxide) detectors…")
"CARBON-MONOXIDE POISONING HAZARD FAILURE TO FOLLOW INSTRUCTIONS COULD RESULT IN SEVERE PERSONAL INJURY OR DEATH DUE TO CARBON-MONOXIDE POISONING, IF COMBUSTION PRODUCTS INFILTRATE INTO THE BUILDING."92-24161-124-12, p. 1
"CHECK THAT FURNACE VENT (AND AIR INTAKE) TERMINAL(S) ARE NOT OBSTRUCTED IN ANY WAY DURING ALL SEASONS."92-24161-124-12, p. 1
"Improper installation, adjustment, alteration, service or maintenance can cause injury property damage or death. Refer to this manual. Installation and service must be performed by a qualified installer, service agency or the gas supplier."92-24161-124-12, p. 1
"HOLES IN THE VENT PIPE OR HEAT EXCHANGER CAN CAUSE TOXIC FUMES TO ENTER THE HOME, RESULTING IN CARBON MONOXIDE POISONING OR DEATH. THE VENT PIPE OR HEAT EXCHANGER MUST BE REPLACED IF THEY LEAK."92-24161-144-09, p. 49

Rheem furnaces not covered yet

Two older modulating families have a Rheem installation manual on the same document server, but their fault tables are not on this page yet: RGFE / RGGE / RGJF (92-24161-75-04) and GFD / GGD / GJD (92-24161-22-21). Their tables run to many pages, and the GFD table's text cannot be read reliably from the file, so they wait rather than risk a wrong transcription.

For Rheem's newest furnaces, the R921, R951, R962, R972 and R97M/R98M models, we did not find an installation manual on a Rheem-hosted page, so this page has no code table for them.

For other brands' schemes, see the Goodman furnace codes hub and the Carrier furnace codes hub.

Frequently asked questions

What does code 57 mean on a Rheem furnace?

It is a pressure switch fault, but the wording depends on the series. On the (-)801T, (-)801S/P, (-)92T and (-)95T it is "PRESS SWITCH STUCK OPEN WHEN SHOULD BE CLOSED"; on the (-)96T, "HIGH PRESSURE SWITCH OPEN"; on the communicating furnaces, "HIGH PRESSURE SWITCH OPEN, INDUCER ON HIGH SPEED". Rheem leaves pressure switches, hoses and venting to a servicer.

Why does my Rheem furnace show 0, H or C?

Those are not faults. Rheem's manuals say the display reads "0" (zero) in standby and shows a letter for the mode: C for cooling or heat-pump heat, F for continuous fan, H for gas heat. Two-stage and communicating furnaces also use a lower-case h or c for low stage.

How do I read a two-digit code on a single-digit display?

The (-)801T and (-)801S/P show the first digit for one second, then the second digit for one second, then pause for half a second and repeat. Code 57 therefore appears as 5, then 7. Each fault is shown at least twice.

My Rheem furnace code is not in any table. What now?

Check that you are reading the display the right way up. Rheem's communicating manuals warn that "the fault codes may be upside-down" and that "If a fault code or operating code is not on these lists, the display may be upside-down." Then confirm the series on the rating plate.

How do I reset a Rheem furnace lockout?

Rheem's single-stage manual says lockouts clear when "the original fault causing the lockout is cleared and power to the unit is cycled off and then back on again"; a one-hour lockout also resets itself after an hour. The older LED flowcharts say to shut off main power, wait 30 seconds and reset. A code that returns needs a servicer.