Generac Error Codes: The Full List, What Each One Means, and How to Clear It

GeneracAir-cooled home standby (Guardian, PowerPact, Next Generation) with Evolution, Evolution 2.0, Sync, and Power Zone 200 controllers; notes on Nexus text alarmsLast updated:

Red light = alarm, and the generator will not run until you clear it. Yellow = warning or maintenance reminder; it keeps running. Generac publishes its alarm codes in families: 1100s overcrank, 1200s overspeed, 1300 low oil pressure, 1400s high temperature, 1500s RPM sense, 1600s underspeed, 1900s undervoltage, 2100s overload, 2750 low battery, 2770/2780 charger, 2098/2099 wiring, 2800 shutdown switch. The reset is the same for nearly all of them — OFF → ENTER → AUTO — but Generac's rule is never clear an alarm without correcting the cause. The table below links each code to its page, with a severity and DIY rating.

How to read the display and the lights

Evolution and Evolution 2.0 controllers (2013 and newer Guardians) show a four-digit code and a text message (on Evolution 2.0 the alarm log alternates them every five seconds), plus status LEDs. From Generac's own definitions:

  • Alarm — solid red. Requires immediate attention; the unit shuts down or refuses to start. Clear it from the panel or press MANUAL to attempt a restart; if it returns, contact a dealer.
  • Warning — yellow. Something needs attention but the unit still operates (charger warnings 2770/2780, for example).
  • Maintenance reminder — yellow. Change oil, inspect battery, service due. It clears only after the maintenance is logged.

Nexus controllers (pre-2013) show text only — overcrank, low oil pressure, RPM sensor failure, under-voltage, under-frequency — with no numbers. The functions map onto the numeric families below. If your Nexus manual says an alarm "cannot be cleared, call service dealer" (under-frequency is one), believe it.

If the unit is enrolled in Mobile Link, the app's status history shows the code number and a one-line message; the messages are quoted in the table where Generac publishes them.

The complete code table

Rows with links have a full page (meaning, reset, diagnosis, parts). Unlinked rows are on Generac's official list and will get their own page as we verify the manual text for each.

Error codes, meanings, severity, and DIY rating
CodeDisplayMeaning (Generac wording)SeverityDIY?
1100OVERCRANKEngine cranks but will not start after 5 crank attemptsUnit will not runCheck, then call
1101OVERCRANK8–9 kW Evolution 1.0 only: cranking limited to 10 cycles to protect the starterUnit will not runCheck, then call
1200–1207OVERSPEEDEngine exceeded the controller's speed limit; family listed by Generac as OverspeedUnit will not runLicensed pro / dealer
1300LOW OIL PRESSURELow oil pressure switch opened while running — check oil level and pressureUnit will not runDIY-friendly
1400–1401HIGH TEMPERATUREEngine over-temperature; family listed by Generac as High TemperatureUnit will not runCheck, then call
1501RPM SENSE LOSSTwin-cylinder, lost RPM while running: air pocket in fuel line, dirty fuel, missing ignition pulseUnit will not runCheck, then call
1505RPM SENSE LOSSTwin-cylinder, lost RPM while cranking: starter motor, missing ignition pulseUnit will not runCheck, then call
1511RPM SENSE LOSSSingle-cylinder, lost RPM while runningUnit will not runCheck, then call
1515RPM SENSE LOSSSingle-cylinder, lost RPM while crankingUnit will not runCheck, then call
1600UNDERSPEEDUnit overloaded — 55 Hz for 30 s on a 60 Hz unit; low fuel supply or throttle (stepper) control problemUnit will not runCheck, then call
1603UNDERSPEEDEngine never reaches 3,600 rpm — check fuel selection and supplyUnit will not runCheck, then call
1900UNDERVOLTAGEOutput below 80 % of nominal for 10 s or moreUnit will not runCheck, then call
1902UNDERVOLTAGEBoth zero-cross signals missing for more than 1.5 s — excitation winding, zero-cross circuit, loose wiring, field boostUnit will not runCheck, then call
1901, 1906, 1903–1916UNDERVOLTAGEUndervoltage variants; individual definitions not published at owner levelUnit will not runLicensed pro / dealer
2098–2099WIRING ERRORFamily listed by Generac as Wiring Error; definition not published at owner levelUnit will not runLicensed pro / dealer
2100–2103OVERLOADFamily listed by Generac as Overload — load exceeds the generator's ratingUnit will not runCheck, then call
2750LOW BATTERYBattery voltage low; listed in Generac's alarm listUnit will not runDIY-friendly
2770CHARGER WARNINGBattery charger fault (yellow)Runs with warningCheck, then call
2780CHARGER MISSING ACCharger has lost its AC supply from the house (yellow)Runs with warningDIY-friendly
2800AUXILIARY SHUTDOWN / SHUTDOWN SWITCHExternal shutdown circuit open — a shutdown switch is at OUnit will not runDIY-friendly
2801AUXILIARY SHUTDOWNSame cause and reset as 2800 per Generac's support articleUnit will not runDIY-friendly

Severity: stop = unit will not run; warn = runs, needs attention. DIY: yes = owner can resolve with the manual; partial = owner-level checks first, then dealer; pro = dealer diagnosis from the start.

How to clear an alarm

Generac's general procedure for Guardian units with Evolution / Sync controllers, from its support article:

  1. Confirm the external shutdown switch on the back panel is at I (closed). On 13 kW and larger units, check the internal switch too.
  2. Press the red OFF button.
  3. Press ENTER as prompted on the display. (The 1300 article says twice; some units prompt once.)
  4. Press the green AUTO button.
  5. To test, press the blue MANUAL button.

Variants:

  • PowerPact 7.5 kW: press OFF twice to reach an active alarm; three times if a maintenance reminder is also showing.
  • Next Generation (Power Zone 200): hold OFF for 3 seconds, then AUTO.
  • Nexus: rocker switch to OFF, ENTER twice, rocker to AUTO. Units without a rocker: OFF button, ENTER twice.
  • Liquid-cooled (Power Zone 410): STOP + ENTER, per Generac's article — the code table above is for air-cooled units only.

During an outage, Generac's restart article notes that a fault shows as a red status light and an error code on the control panel or in Mobile Link; clear it with the sequence above and return the unit to AUTO. If it runs in MANUAL but the house stays dark, the problem is on the transfer-switch side and a dealer is the next call.

Symptoms without a code

Not every problem posts a number.

  • Runs, but the house has no power. The generator is producing voltage (no 1900-series alarm) but the transfer switch didn't transfer, or its breaker is off. Check the generator's main breaker (on the unit) and the transfer switch. Never bridge this with a cord into a wall outlet — Generac's own page on backfeeding calls it illegal under the NEC and a lethal hazard to line workers.
  • Starts, runs a few seconds, dies, no alarm. Watch the display on the next attempt — the alarm may post after the third or fourth try (RPM sense or low oil pressure).
  • Didn't exercise this week. Check the exercise schedule in the menu, the yellow LED, and the battery.
  • Yellow light with "Inspect Battery" / "Change Oil" text. That's a maintenance reminder. Do the service, then clear the reminder from the controller's maintenance menu (it will not clear from the alarm reset).
  • Dead display. Battery disconnected or dead; control panel fuse (0D7178T on 10–24 kW units); or the charger's house breaker tripped.

Maintenance that prevents most codes

From the 10–26 kW owner's manual: oil and filter at 25 hours, then every 2 years or 200 hours; air filter, spark plugs, and valve clearance every 4 years or 400 hours; battery inspection yearly. Most of the pages linked above end with "it was the battery" or "it was fuel supply," and both are on the yearly checklist.

Sizing matters too. Underspeed (1600) and overload (2100) are not repairs, they're a generator that was never big enough for a well pump plus the AC. The wattage calculator shows what your essential loads add up to.

Not sure the generator can carry the load?Generator Wattage Calculator Running watts, the largest starting surge, and a generator class from manufacturer charts.

Parts and supplies mentioned on this page

Consumables for the yearly checklist. Generac keys its kits to your model number (G00xxxxx), so match the kit to the model, not the kW.

Frequently asked questions

What's the difference between a Generac alarm, warning, and maintenance reminder?

Per Generac: alarms are red and stop the unit; warnings are yellow and the unit keeps operating; maintenance reminders are yellow and clear only after the maintenance is logged in the menu.

Is Generac code 1902 "under speed"?

No. Generac's list puts 1900–1916 under Undervoltage and 1600–1603 under Underspeed. The mislabel is common on third-party sites.

Can I clear any alarm and let the generator run?

You can clear it, but Generac's support page says never to clear an alarm without correcting the cause. Several alarms (low oil pressure, high temperature, overspeed) exist to stop the engine from destroying itself.

Why doesn't my older Generac show a number?

Nexus controllers (pre-2013) show text alarms only. The numeric codes arrived with the Evolution controller in 2013. The alarms map one-to-one onto the families in the table.

Where do I find the code if I missed it?

MAIN MENU → HISTORY → ALARM LOG on the controller, or the status history in the Mobile Link app if the unit is enrolled.